OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | NECB 2011-SmallHotel-NECB HDD Method-CAN_BC_Comox.718930_CWEC.epw created: 2017-06-30 16:27:49 +0000 | building_name |
| Net Site Energy | 2,724,965 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 63.08 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | Comox BC CAN WYEC2-B-24292 WMO#=718930 |
| Latitude | 49.72 |
| Longitude | -124.9 |
| Elevation | 79 (ft) |
| Time Zone | -8.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| COMOX ANN CLG .4% CONDNS DB=>MWB | 80.06 | 15.3 | 63.32 | Wetbulb [F] | 7.61 | 340.0 |
| COMOX ANN CLG .4% CONDNS WB=>MDB | 75.92 | 15.3 | 64.76 | Wetbulb [F] | 7.61 | 340.0 |
| COMOX ANN HTG 99.6% CONDNS DB | 22.28 | 0.0 | 22.28 | Wetbulb [F] | 6.93 | 300.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 100.75 |
| During Cooling | 0.0 |
| During Occupied Heating | 100.75 |
| During Occupied Cooling | 0.0 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 1.8 |
| Cooling | 1.8 |
Annual Overview
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 894,436 |
| Cooling | 43,078 |
| Interior Lighting | 372,615 |
| Exterior Lighting | 0 |
| Interior Equipment | 93,379 |
| Exterior Equipment | 0 |
| Fans | 150,892 |
| Pumps | 18,890 |
| Heat Rejection | 76 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 1,151,588 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 678,940 |
| Natural Gas | 2,046,024 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 0 |
| Cooling | 12,625 |
| Interior Lighting | 109,203 |
| Exterior Lighting | 0 |
| Interior Equipment | 27,367 |
| Exterior Equipment | 0 |
| Fans | 44,222 |
| Pumps | 5,536 |
| Heat Rejection | 22 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 0 |
| Refrigeration | 0 |
| Generators | 0 |
| End Use | Consumption (therms) |
|---|---|
| Heating | 8,946 |
| Cooling | 0 |
| Interior Lighting | 0 |
| Exterior Lighting | 0 |
| Interior Equipment | 0 |
| Exterior Equipment | 0 |
| Fans | 0 |
| Pumps | 0 |
| Heat Rejection | 0 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 11,518 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | |||||||||||||
| Cooling | 16.75 | 64.9 | 166.73 | 281.28 | 842.65 | 1920.24 | 3467.22 | 3684.97 | 1755.94 | 331.78 | 80.47 | 12.87 | 12625.79 |
| Interior Lighting | 9274.53 | 8378.94 | 9308.33 | 8924.72 | 9308.33 | 8998.53 | 9234.53 | 9308.33 | 8958.56 | 9274.53 | 8998.53 | 9234.53 | 109202.39 |
| Exterior Lighting | |||||||||||||
| Interior Equipment | 2324.35 | 2099.92 | 2335.12 | 2232.89 | 2335.12 | 2256.72 | 2311.29 | 2335.12 | 2243.66 | 2324.35 | 2256.72 | 2311.29 | 27366.55 |
| Exterior Equipment | |||||||||||||
| Fans | 3411.81 | 3102.22 | 3479.89 | 3408.53 | 3742.17 | 3963.83 | 4424.11 | 4487.5 | 3923.94 | 3541.81 | 3330.69 | 3406.97 | 44223.47 |
| Pumps | 460.31 | 415.26 | 471.05 | 475.46 | 515.31 | 477.14 | 410.55 | 409.8 | 492.99 | 499.08 | 447.39 | 462.46 | 5536.79 |
| Heat Rejection | 0.09 | 0.05 | 0.1 | 0.14 | 0.51 | 2.51 | 6.71 | 9.18 | 3.51 | 0.23 | 0.09 | 0.07 | 23.2 |
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | |||||||||||||
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 15487.83 | 14061.29 | 15761.22 | 15323.01 | 16744.09 | 17618.97 | 19854.42 | 20234.9 | 17378.6 | 15971.77 | 15113.89 | 15428.2 | 198978.2 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 155.81 | 103.5 | 109.16 | 73.52 | 49.04 | 26.35 | 13.73 | 12.23 | 31.46 | 70.6 | 105.82 | 143.23 | 894.44 |
| Cooling | |||||||||||||
| Interior Lighting | |||||||||||||
| Exterior Lighting | |||||||||||||
| Interior Equipment | |||||||||||||
| Exterior Equipment | |||||||||||||
| Fans | |||||||||||||
| Pumps | |||||||||||||
| Heat Rejection | |||||||||||||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 103.42 | 94.28 | 103.61 | 97.73 | 97.97 | 91.65 | 92.11 | 91.41 | 89.23 | 94.5 | 94.71 | 100.95 | 1151.58 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 259.23 | 197.79 | 212.77 | 171.25 | 147.01 | 117.99 | 105.84 | 103.64 | 120.69 | 165.1 | 200.53 | 244.18 | 2046.02 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | ||||||||||||
| Cooling | 0.3669 | 1.4903 | 2.3847 | 3.027 | 5.7306 | 11.3514 | 12.2045 | 11.696 | 11.5052 | 2.8668 | 1.3495 | 0.2567 |
| Interior Lighting | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 | 26.9881 |
| Exterior Lighting | ||||||||||||
| Interior Equipment | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 | 6.4671 |
| Exterior Equipment | ||||||||||||
| Fans | 4.9064 | 5.3977 | 5.7921 | 6.0373 | 7.0843 | 8.1591 | 8.1692 | 8.3315 | 8.329 | 5.9872 | 5.3371 | 4.8576 |
| Pumps | 0.6124 | 0.6124 | 0.6124 | 0.7883 | 0.7883 | 0.1945 | 0.1945 | 0.1945 | 0.1945 | 0.7883 | 0.6124 | 0.6124 |
| Heat Rejection | 0.0157 | 0.0128 | 0.0267 | 0.0257 | ||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | ||||||||||||
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 39.34 | 40.96 | 42.24 | 43.31 | 47.06 | 53.18 | 54.04 | 53.7 | 53.51 | 43.1 | 40.75 | 39.18 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 467.6858 | 268.2735 | 283.3648 | 204.2954 | 196.1569 | 86.5346 | 54.9272 | 51.9517 | 124.5692 | 253.8448 | 313.1739 | 396.3547 |
| Cooling | ||||||||||||
| Interior Lighting | ||||||||||||
| Exterior Lighting | ||||||||||||
| Interior Equipment | ||||||||||||
| Exterior Equipment | ||||||||||||
| Fans | ||||||||||||
| Pumps | ||||||||||||
| Heat Rejection | ||||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 279.3165 | 292.2626 | 287.4164 | 290.3504 | 239.0723 | 253.8867 | 233.834 | 232.2336 | 228.1514 | 234.3364 | 251.2719 | 255.1122 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 747.0 | 560.54 | 570.78 | 494.65 | 435.23 | 340.42 | 288.76 | 284.19 | 352.72 | 488.18 | 564.45 | 651.47 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Customized opaque construction {209e294c-b60e-4a3f-95b5-91923332df9b} to conductance of 0.278 | 16,258 | 92 | 20.43 |
| Customized opaque construction {a85bebb7-3cff-45d9-871f-8f5b24a28d31} to conductance of 0.183 | 10,800 | 16 | 31.03 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 | 1,983 | 103 | 0.3874 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F | 5,670 | Space Function | Corr. >= 2.4m wide-sch-F |
| Space Function Electrical/Mechanical-sch-F | 1,215 | Space Function | Electrical/Mechanical-sch-F |
| Space Function Gym - fitness | 351 | Space Function | Gym - fitness |
| Space Function Hotel/Motel - lobby | 1,755 | Space Function | Hotel/Motel - lobby |
| Space Function Hway lodging - rooms | 27,271 | Space Function | Hway lodging - rooms |
| Space Function Lobby - elevator | 648 | Space Function | Lobby - elevator |
| Space Function Lounge/recreation | 351 | Space Function | Lounge/recreation |
| Space Function Office - enclosed | 1,404 | Space Function | Office - enclosed |
| Space Function Stairway-sch-F | 1,728 | Space Function | Stairway-sch-F |
| Space Function Storage area - occsens | 2,457 | Space Function | Storage area - occsens |
| Space Function Washroom-sch-F | 351 | Space Function | Washroom-sch-F |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Lights Definition | 0.6596 | W/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Electrical/Mechanical-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Lights Definition | 1.2356 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Gym - fitness People Definition | 0.0186 | people/ft^2 | 1.0 |
| Space Function Gym - fitness Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Lights Definition | 0.9104 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Ventilation (outdoor air method Sum) | 0.8600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hotel/Motel - lobby People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Lights Definition | 1.0591 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Ventilation (outdoor air method Sum) | 0.2850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hway lodging - rooms People Definition | 0.0037 | people/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Lights Definition | 0.7525 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Ventilation (outdoor air method Sum) | 0.1100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lobby - elevator People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lobby - elevator Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Lights Definition | 0.6410 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Ventilation (outdoor air method Sum) | 0.8100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lounge/recreation People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lounge/recreation Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Lights Definition | 0.7860 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Ventilation (outdoor air method Sum) | 0.1850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Office - enclosed People Definition | 0.0046 | people/ft^2 | 1.0 |
| Space Function Office - enclosed Elec Equip Definition | 0.6968 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Lights Definition | 1.1055 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Ventilation (outdoor air method Sum) | 0.0850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Stairway-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Stairway-sch-F Lights Definition | 0.6875 | W/ft^2 | 1.0 |
| Space Function Stairway-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Storage area - occsens People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Storage area - occsens Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Lights Definition | 0.5686 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Ventilation (outdoor air method Sum) | 0.0700 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Washroom-sch-F People Definition | 0.0031 | people/ft^2 | 1.0 |
| Space Function Washroom-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Lights Definition | 0.8779 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.66 | 1068.58 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3180.56 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 433.73 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 1291.67 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 1067.63 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3177.78 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION GYM - FITNESS LIGHTS | SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.91 | 319.57 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1725.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN SPACE FUNCTION HOTEL/MOTEL - LOBBY LIGHTS | SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1.06 | 1858.83 | NECB-H-LIGHTING | 151.2 | 151.2 | 0.0000 | 14655.56 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION LOUNGE/RECREATION LIGHTS | SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.79 | 275.87 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1488.89 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS | SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1.11 | 1552.17 | NECB-A-LIGHTING | 56.27 | 56.27 | 0.0000 | 4552.78 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 598.7 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 1711.11 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION WASHROOM-SCH-F LIGHTS | SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.88 | 308.17 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 916.67 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
| InteriorEquipment:Electricity:Zone:SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 238.89 |
| InteriorEquipment:Electricity:Zone:SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3213.89 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3622.22 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 280.56 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
Exterior Lighting
No Data to Show for Exterior Lighting
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Employeeloungeflr1 Service Water Use 0.02gal/min | Main Service Water Loop | Employeeloungeflr1 Service Water Use Def 0.02gal/min | EmployeeLoungeFlr1 | 0.02 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Exercisecenterflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Exercisecenterflr1 Service Water Use Def 0.05gal/min | ExerciseCenterFlr1 | 0.05 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Frontloungeflr1 Service Water Use 0.04gal/min | Main Service Water Loop | Frontloungeflr1 Service Water Use Def 0.04gal/min | FrontLoungeFlr1 | 0.04 | NECB-H-Service Water Heating | 140.0 to 140.0 |
| Frontofficeflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Frontofficeflr1 Service Water Use Def 0.05gal/min | FrontOfficeFlr1 | 0.05 | NECB-A-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr1 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr1 Service Water Use Def 0.0gal/min | FrontStorageFlr1 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr2 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr2 Service Water Use Def 0.0gal/min | FrontStorageFlr2 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr3 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr3 Service Water Use Def 0.0gal/min | FrontStorageFlr3 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr4 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr4 Service Water Use Def 0.0gal/min | FrontStorageFlr4 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Guestroom101 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.07gal/min | GuestRoom101 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom102 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.07gal/min | GuestRoom102 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom103 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.07gal/min | GuestRoom103 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom104 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.07gal/min | GuestRoom104 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom105 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.07gal/min | GuestRoom105 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom201 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.07gal/min | GuestRoom201 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom202_205 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.27gal/min | GuestRoom202_205 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom206_208 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.22gal/min | GuestRoom206_208 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom209_212 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.27gal/min | GuestRoom209_212 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom213 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.07gal/min | GuestRoom213 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom214 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.07gal/min | GuestRoom214 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom215_218 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.27gal/min | GuestRoom215_218 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom219 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.07gal/min | GuestRoom219 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom220_223 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.27gal/min | GuestRoom220_223 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom224 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.07gal/min | GuestRoom224 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom301 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.07gal/min | GuestRoom301 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom302_305 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.27gal/min | GuestRoom302_305 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom306_308 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.22gal/min | GuestRoom306_308 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom309_312 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.27gal/min | GuestRoom309_312 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom313 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.07gal/min | GuestRoom313 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom314 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.07gal/min | GuestRoom314 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom315_318 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.27gal/min | GuestRoom315_318 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom319 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.07gal/min | GuestRoom319 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom320_323 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.27gal/min | GuestRoom320_323 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom324 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.07gal/min | GuestRoom324 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom401 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.07gal/min | GuestRoom401 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom402_405 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.27gal/min | GuestRoom402_405 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom406_408 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.22gal/min | GuestRoom406_408 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom409_412 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.27gal/min | GuestRoom409_412 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom413 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.07gal/min | GuestRoom413 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom414 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.07gal/min | GuestRoom414 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom415_418 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.27gal/min | GuestRoom415_418 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom419 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.07gal/min | GuestRoom419 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom420_423 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.27gal/min | GuestRoom420_423 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom424 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.07gal/min | GuestRoom424 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Laundryroomflr1 Service Water Use 0.03gal/min | Main Service Water Loop | Laundryroomflr1 Service Water Use Def 0.03gal/min | LaundryRoomFlr1 | 0.03 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr1 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr1 Service Water Use Def 0.01gal/min | RearStorageFlr1 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr2 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr2 Service Water Use Def 0.01gal/min | RearStorageFlr2 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr3 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr3 Service Water Use Def 0.01gal/min | RearStorageFlr3 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr4 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr4 Service Water Use Def 0.01gal/min | RearStorageFlr4 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | 35.7 | 40.2 | 42.1 | 47.4 | 52.3 | 57.9 | 62.8 | 63.1 | 56.3 | 48.6 | 41.8 | 37.9 |
| Cooling Load (MBtu) | 0.06 | 0.22 | 0.57 | 0.96 | 2.88 | 6.55 | 11.83 | 12.57 | 5.99 | 1.13 | 0.27 | 0.04 |
| Heating Load (MBtu) | 155.81 | 103.5 | 109.16 | 73.52 | 49.04 | 26.35 | 13.73 | 12.23 | 31.46 | 70.6 | 105.82 | 143.23 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 158 | 848 | 3698 | 1407 | 2649 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 12 | 1933 | 2505 | 4310 | 0 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 28 | 2182 | 2262 | 4288 | 0 | 0 | 0 | 0 | 0 | 0 | 73.5 (F) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 13 | 13 | 0 | 0 | 84 | 328 | 608 | 3297 | 1735 | 2708 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2491 | 748 | 698 | 4023 | 430 | 370 | 0 | 0 | 0 | 0 | 0 | 0 | 69.2 (F) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2245 | 1090 | 617 | 4087 | 382 | 339 | 0 | 0 | 0 | 0 | 0 | 0 | 69.3 (F) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2240 | 1103 | 613 | 4084 | 376 | 344 | 0 | 0 | 0 | 0 | 0 | 0 | 69.3 (F) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2936 | 773 | 342 | 3900 | 390 | 419 | 0 | 0 | 0 | 0 | 0 | 0 | 69.0 (F) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 379 | 752 | 673 | 3644 | 1268 | 2042 | 2 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 59 | 59 | 0 | 0 | 5 | 137 | 234 | 2223 | 2978 | 2812 | 364 | 7 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 26 | 978 | 4562 | 1145 | 2046 | 3 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 4 | 4 | 0 | 0 | 10 | 159 | 708 | 1634 | 2265 | 3731 | 253 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 271 | 590 | 665 | 4509 | 1223 | 1502 | 0 | 0 | 0 | 0 | 0 | 0 | 71.6 (F) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 185 | 561 | 673 | 4515 | 1253 | 1573 | 0 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 230 | 548 | 648 | 4535 | 1220 | 1579 | 0 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 757 | 437 | 536 | 4551 | 1010 | 1469 | 0 | 0 | 0 | 0 | 0 | 0 | 71.3 (F) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 31 | 652 | 1607 | 2630 | 1623 | 2108 | 109 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 3 | 341 | 1605 | 2869 | 1642 | 2184 | 116 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 7 | 487 | 1597 | 2813 | 1600 | 2128 | 128 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 648 | 1086 | 1189 | 2568 | 1299 | 1797 | 163 | 10 | 0 | 0 | 0 | 0 | 71.1 (F) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 34 | 1922 | 2760 | 4044 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 39 | 2036 | 2665 | 4020 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 237 | 2944 | 2167 | 3412 | 0 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 40 | 1497 | 2508 | 4715 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 32 | 1323 | 2394 | 5011 | 0 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 20 | 20 | 0 | 0 | 0 | 19 | 237 | 2499 | 1949 | 4056 | 0 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1 | 1 | 0 | 0 | 0 | 0 | 3 | 773 | 2586 | 5398 | 0 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 8 | 1222 | 2618 | 4912 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 5 | 1140 | 2623 | 4992 | 0 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 76 | 2258 | 2343 | 4083 | 0 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 10 | 863 | 2247 | 5640 | 0 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 15 | 736 | 2064 | 5945 | 0 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 41 | 1362 | 2386 | 4971 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 13 | 482 | 1882 | 6383 | 0 | 0 | 0 | 0 | 0 | 0 | 74.2 (F) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1 | 1 | 0 | 0 | 0 | 0 | 21 | 717 | 2150 | 5872 | 0 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 11 | 11 | 0 | 0 | 2 | 62 | 398 | 2982 | 1662 | 3654 | 0 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 24 | 1306 | 2493 | 4937 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 34 | 1477 | 2418 | 4831 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 31 | 1419 | 2469 | 4841 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 143 | 2518 | 2130 | 3969 | 0 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 27 | 1126 | 2180 | 5427 | 0 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 19 | 785 | 1997 | 5959 | 0 | 0 | 0 | 0 | 0 | 0 | 74.0 (F) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 36 | 1357 | 2320 | 5047 | 0 | 0 | 0 | 0 | 0 | 0 | 73.7 (F) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 16 | 680 | 1972 | 6092 | 0 | 0 | 0 | 0 | 0 | 0 | 74.1 (F) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 0 | 25 | 1074 | 2165 | 5496 | 0 | 0 | 0 | 0 | 0 | 0 | 73.9 (F) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 32 | 32 | 0 | 0 | 276 | 383 | 543 | 3549 | 1444 | 2565 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 30 | 30 | 0 | 0 | 95 | 283 | 501 | 2953 | 1653 | 3275 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 27 | 27 | 0 | 0 | 100 | 284 | 521 | 2968 | 1618 | 3269 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 29 | 29 | 0 | 0 | 96 | 281 | 518 | 2959 | 1663 | 3243 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 17 | 17 | 0 | 0 | 130 | 370 | 632 | 3347 | 1525 | 2756 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 15 | 15 | 0 | 0 | 63 | 264 | 496 | 2623 | 1743 | 3571 | 0 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 25 | 25 | 0 | 0 | 68 | 232 | 456 | 2363 | 1681 | 3960 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 15 | 15 | 0 | 0 | 64 | 294 | 580 | 2811 | 1836 | 3175 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 26 | 26 | 0 | 0 | 65 | 225 | 449 | 2345 | 1705 | 3971 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 16 | 16 | 0 | 0 | 64 | 262 | 516 | 2630 | 1700 | 3588 | 0 | 0 | 0 | 0 | 0 | 0 | 72.8 (F) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 532 | 1291 | 1152 | 2312 | 1491 | 1838 | 137 | 7 | 0 | 0 | 0 | 0 | 71.2 (F) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 127 | 836 | 3728 | 1358 | 2711 | 0 | 0 | 0 | 0 | 0 | 0 | 72.5 (F) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 10 | 455 | 767 | 3828 | 1259 | 2441 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 9 | 9 | 0 | 0 | 42 | 263 | 692 | 4118 | 1785 | 1860 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 18 | 18 | 0 | 0 | 23 | 154 | 649 | 3867 | 1880 | 2187 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 17 | 17 | 0 | 0 | 43 | 215 | 629 | 3937 | 1857 | 2079 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 39 | 39 | 0 | 0 | 447 | 512 | 539 | 4324 | 1493 | 1445 | 0 | 0 | 0 | 0 | 0 | 0 | 71.5 (F) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1219 | 1079 | 976 | 2666 | 1226 | 1507 | 87 | 0 | 0 | 0 | 0 | 0 | 70.6 (F) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1164 | 1056 | 945 | 2689 | 1225 | 1581 | 100 | 0 | 0 | 0 | 0 | 0 | 70.7 (F) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 1277 | 995 | 908 | 2711 | 1169 | 1570 | 130 | 0 | 0 | 0 | 0 | 0 | 70.6 (F) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2143 | 719 | 756 | 2661 | 992 | 1343 | 135 | 11 | 0 | 0 | 0 | 0 | 70.0 (F) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 32 | 690 | 3713 | 1356 | 2969 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 2500 | 1850 | 1742 | 1419 | 871 | 331 | 47 | 0 | 0 | 0 | 0 | 0 | 35.1 (%) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3025 | 1817 | 1632 | 1280 | 768 | 224 | 14 | 0 | 0 | 0 | 0 | 0 | 33.8 (%) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3010 | 1825 | 1604 | 1298 | 765 | 241 | 17 | 0 | 0 | 0 | 0 | 0 | 33.9 (%) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 2747 | 1763 | 1588 | 1276 | 854 | 441 | 90 | 1 | 0 | 0 | 0 | 0 | 34.9 (%) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 2144 | 1362 | 1407 | 1170 | 1021 | 810 | 502 | 288 | 52 | 4 | 0 | 0 | 38.7 (%) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 2174 | 1385 | 1384 | 1162 | 991 | 817 | 505 | 284 | 57 | 1 | 0 | 0 | 38.7 (%) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 2180 | 1380 | 1385 | 1161 | 990 | 815 | 507 | 281 | 60 | 1 | 0 | 0 | 38.7 (%) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 2121 | 1365 | 1369 | 1159 | 978 | 790 | 555 | 307 | 104 | 12 | 0 | 0 | 39.1 (%) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1131 | 1190 | 1651 | 1707 | 1536 | 900 | 503 | 137 | 5 | 0 | 0 | 0 | 41.0 (%) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 115 | 286 | 579 | 904 | 1273 | 1670 | 1832 | 953 | 600 | 288 | 150 | 110 | 53.4 (%) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 897 | 1205 | 1625 | 1693 | 1536 | 1049 | 590 | 163 | 2 | 0 | 0 | 0 | 41.9 (%) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1648 | 1521 | 1801 | 2263 | 1145 | 382 | 0 | 0 | 0 | 0 | 0 | 0 | 37.4 (%) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 2636 | 1655 | 1583 | 1344 | 876 | 545 | 121 | 0 | 0 | 0 | 0 | 0 | 35.4 (%) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 2691 | 1641 | 1584 | 1366 | 840 | 524 | 114 | 0 | 0 | 0 | 0 | 0 | 35.2 (%) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 2687 | 1650 | 1591 | 1373 | 831 | 516 | 112 | 0 | 0 | 0 | 0 | 0 | 35.2 (%) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 2584 | 1649 | 1550 | 1351 | 944 | 542 | 127 | 13 | 0 | 0 | 0 | 0 | 35.6 (%) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1971 | 1689 | 1775 | 1674 | 1034 | 512 | 102 | 3 | 0 | 0 | 0 | 0 | 36.8 (%) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 2104 | 1697 | 1732 | 1573 | 985 | 563 | 98 | 8 | 0 | 0 | 0 | 0 | 36.6 (%) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 2071 | 1693 | 1729 | 1600 | 976 | 571 | 112 | 8 | 0 | 0 | 0 | 0 | 36.7 (%) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 1928 | 1685 | 1753 | 1733 | 970 | 558 | 131 | 2 | 0 | 0 | 0 | 0 | 36.9 (%) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 30 | 131 | 492 | 1176 | 2191 | 2572 | 1480 | 587 | 98 | 3 | 0 | 0 | 50.3 (%) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 30 | 128 | 493 | 1169 | 2173 | 2559 | 1493 | 609 | 102 | 4 | 0 | 0 | 50.4 (%) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 25 | 115 | 434 | 1073 | 2012 | 2554 | 1690 | 702 | 141 | 14 | 0 | 0 | 51.1 (%) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 40 | 202 | 540 | 1282 | 2317 | 2412 | 1391 | 502 | 68 | 6 | 0 | 0 | 49.7 (%) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 50 | 223 | 549 | 1383 | 2337 | 2398 | 1324 | 436 | 56 | 4 | 0 | 0 | 49.3 (%) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 89 | 341 | 895 | 1821 | 2516 | 1959 | 885 | 233 | 21 | 0 | 0 | 0 | 47.3 (%) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 61 | 257 | 774 | 1847 | 2568 | 2090 | 929 | 217 | 17 | 0 | 0 | 0 | 47.7 (%) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 56 | 235 | 705 | 1733 | 2499 | 2147 | 1050 | 302 | 33 | 0 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 58 | 236 | 709 | 1735 | 2471 | 2126 | 1073 | 319 | 33 | 0 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 48 | 201 | 622 | 1507 | 2403 | 2330 | 1201 | 406 | 42 | 0 | 0 | 0 | 49.0 (%) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 86 | 314 | 807 | 1813 | 2489 | 2056 | 959 | 214 | 22 | 0 | 0 | 0 | 47.5 (%) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 98 | 349 | 849 | 1841 | 2428 | 1996 | 955 | 223 | 21 | 0 | 0 | 0 | 47.3 (%) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 71 | 277 | 718 | 1654 | 2346 | 2109 | 1146 | 384 | 50 | 5 | 0 | 0 | 48.4 (%) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 114 | 383 | 939 | 1942 | 2445 | 1895 | 850 | 173 | 19 | 0 | 0 | 0 | 46.8 (%) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 99 | 328 | 870 | 1842 | 2506 | 2037 | 879 | 178 | 21 | 0 | 0 | 0 | 47.2 (%) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 94 | 331 | 889 | 1734 | 2400 | 1976 | 952 | 338 | 44 | 2 | 0 | 0 | 47.6 (%) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 60 | 243 | 737 | 1759 | 2508 | 2109 | 1007 | 305 | 32 | 0 | 0 | 0 | 48.1 (%) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 58 | 239 | 727 | 1723 | 2511 | 2124 | 1033 | 309 | 36 | 0 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 56 | 240 | 726 | 1721 | 2487 | 2110 | 1059 | 325 | 36 | 0 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 48 | 210 | 615 | 1506 | 2398 | 2314 | 1211 | 409 | 47 | 2 | 0 | 0 | 49.0 (%) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 86 | 312 | 812 | 1781 | 2510 | 2042 | 971 | 220 | 26 | 0 | 0 | 0 | 47.5 (%) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 110 | 366 | 896 | 1889 | 2457 | 1928 | 901 | 192 | 21 | 0 | 0 | 0 | 47.1 (%) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 78 | 281 | 760 | 1667 | 2371 | 2059 | 1105 | 381 | 52 | 6 | 0 | 0 | 48.2 (%) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 112 | 372 | 918 | 1932 | 2453 | 1897 | 881 | 175 | 20 | 0 | 0 | 0 | 46.9 (%) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 88 | 313 | 829 | 1774 | 2531 | 2047 | 947 | 206 | 25 | 0 | 0 | 0 | 47.5 (%) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 197 | 415 | 1070 | 1770 | 2237 | 1678 | 908 | 394 | 83 | 8 | 0 | 0 | 47.0 (%) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 126 | 340 | 962 | 1811 | 2416 | 1721 | 940 | 371 | 70 | 3 | 0 | 0 | 47.4 (%) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 130 | 336 | 960 | 1813 | 2416 | 1727 | 941 | 358 | 76 | 3 | 0 | 0 | 47.4 (%) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 128 | 335 | 959 | 1807 | 2403 | 1731 | 947 | 373 | 73 | 4 | 0 | 0 | 47.4 (%) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 120 | 330 | 884 | 1686 | 2323 | 1852 | 1046 | 413 | 97 | 9 | 0 | 0 | 47.9 (%) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 160 | 373 | 1009 | 1870 | 2365 | 1680 | 885 | 352 | 59 | 7 | 0 | 0 | 47.0 (%) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 175 | 387 | 1071 | 1965 | 2309 | 1615 | 871 | 309 | 54 | 4 | 0 | 0 | 46.7 (%) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 158 | 367 | 970 | 1807 | 2296 | 1640 | 1004 | 389 | 114 | 15 | 0 | 0 | 47.4 (%) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 173 | 388 | 1077 | 1965 | 2311 | 1613 | 872 | 306 | 51 | 4 | 0 | 0 | 46.7 (%) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 162 | 371 | 1014 | 1862 | 2368 | 1678 | 900 | 339 | 59 | 7 | 0 | 0 | 47.0 (%) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1710 | 1596 | 1814 | 1787 | 1083 | 624 | 144 | 2 | 0 | 0 | 0 | 0 | 37.6 (%) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 2805 | 1864 | 1739 | 1350 | 726 | 256 | 20 | 0 | 0 | 0 | 0 | 0 | 34.2 (%) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 2714 | 1837 | 1740 | 1389 | 760 | 294 | 26 | 0 | 0 | 0 | 0 | 0 | 34.5 (%) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 2846 | 1684 | 1570 | 1264 | 800 | 491 | 105 | 0 | 0 | 0 | 0 | 0 | 34.8 (%) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 2943 | 1695 | 1553 | 1261 | 774 | 448 | 86 | 0 | 0 | 0 | 0 | 0 | 34.5 (%) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 2922 | 1680 | 1547 | 1269 | 789 | 453 | 100 | 0 | 0 | 0 | 0 | 0 | 34.6 (%) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 2710 | 1653 | 1503 | 1272 | 908 | 562 | 136 | 16 | 0 | 0 | 0 | 0 | 35.4 (%) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 1700 | 1616 | 1708 | 1783 | 1078 | 651 | 213 | 11 | 0 | 0 | 0 | 0 | 37.9 (%) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 1786 | 1609 | 1675 | 1802 | 1026 | 657 | 196 | 9 | 0 | 0 | 0 | 0 | 37.7 (%) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 1777 | 1609 | 1687 | 1801 | 1033 | 657 | 188 | 8 | 0 | 0 | 0 | 0 | 37.7 (%) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 1687 | 1503 | 1718 | 1768 | 1179 | 650 | 220 | 35 | 0 | 0 | 0 | 0 | 38.1 (%) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1446 | 1572 | 1925 | 1770 | 1320 | 597 | 122 | 8 | 0 | 0 | 0 | 0 | 38.3 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.79 | 107.64 | 0.09 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.91 | 53.82 | 0.09 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 1.06 | 107.64 | 0.23 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 215.06 | 0.7 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1053.03 | Yes | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.57 | 1075.31 | 0.09 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 1.24 | 2173.88 | 0.09 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.24 | 2173.88 | 0.09 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.88 | 322.59 | 0.09 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Conditioned Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Unconditioned Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.39 (ton) | 0.43 (ton) | 218.24 | 239.43 | 7/21 17:15:00 | 77.54 | 0.01 |
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 3.26 (kBtu/h) | 4.24 (kBtu/h) | 78.4 | 101.71 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.31 (ton) | 0.34 (ton) | 171.63 | 188.58 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.2 (kBtu/h) | 1.55 (kBtu/h) | 29.66 | 80.52 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.82 (kBtu/h) | 3.67 (kBtu/h) | 67.8 | 86.87 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.47 (ton) | 0.52 (ton) | 260.62 | 286.05 | 7/21 15:00:00 | 80.06 | 0.01 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 10.24 (kBtu/h) | 13.31 (kBtu/h) | 243.67 | 315.71 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 77.92 | 0.01 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Heating | 0.58 (kBtu/h) | 0.76 (kBtu/h) | 14.83 | 131.37 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 131.37 | 7/21 17:00:00 | 77.92 | 0.01 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Heating | 0.27 (kBtu/h) | 0.35 (kBtu/h) | 6.36 | 131.37 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 31.78 | 131.37 | 7/21 17:00:00 | 77.92 | 0.01 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Heating | 0.45 (kBtu/h) | 0.58 (kBtu/h) | 10.59 | 131.37 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 131.37 | 7/21 14:15:00 | 80.06 | 0.01 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Heating | 1.43 (kBtu/h) | 1.86 (kBtu/h) | 33.9 | 131.37 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.18 (ton) | 0.19 (ton) | 97.47 | 105.94 | 7/21 13:15:00 | 79.48 | 0.01 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.06 (kBtu/h) | 1.37 (kBtu/h) | 25.43 | 65.69 | 12/21 10:00:00 | 22.28 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.23 (ton) | 0.26 (ton) | 129.25 | 300.88 | 7/21 13:00:00 | 79.29 | 0.01 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 0.54 (kBtu/h) | 0.7 (kBtu/h) | 12.71 | 300.88 | 12/21 10:00:00 | 22.28 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Cooling | 0.8 (ton) | 0.88 (ton) | 444.96 | 500.06 | 7/21 19:45:00 | 72.82 | 0.01 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Heating | 0.0 (kBtu/h) | 0.0 (kBtu/h) | 0.0 | 500.06 | 22.28 | 0.0 | |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Cooling | 0.74 (ton) | 0.82 (ton) | 411.06 | 451.32 | 7/21 15:00:00 | 80.06 | 0.01 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Heating | 2.65 (kBtu/h) | 3.45 (kBtu/h) | 61.45 | 118.66 | 12/21 08:00:00 | 22.28 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Heating | 1.86 (kBtu/h) | 2.41 (kBtu/h) | 44.5 | 57.21 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 1.52 (kBtu/h) | 1.98 (kBtu/h) | 36.02 | 46.62 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 1.77 (kBtu/h) | 2.3 (kBtu/h) | 42.38 | 55.09 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 36.02 | 38.14 | 7/21 14:45:00 | 80.06 | 0.01 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 2.65 (kBtu/h) | 3.44 (kBtu/h) | 63.57 | 82.64 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 25.43 | 7/21 14:00:00 | 80.06 | 0.01 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 0.72 (kBtu/h) | 0.93 (kBtu/h) | 16.95 | 21.19 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 79.14 | 0.01 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Heating | 0.52 (kBtu/h) | 0.67 (kBtu/h) | 12.71 | 16.95 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 79.14 | 0.01 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Heating | 0.71 (kBtu/h) | 0.92 (kBtu/h) | 16.95 | 21.19 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 33.9 | 7/21 14:00:00 | 80.06 | 0.01 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Heating | 1.47 (kBtu/h) | 1.91 (kBtu/h) | 36.02 | 44.5 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 0.53 (kBtu/h) | 0.69 (kBtu/h) | 12.71 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 0.64 (kBtu/h) | 0.83 (kBtu/h) | 14.83 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.09 (kBtu/h) | 1.41 (kBtu/h) | 25.43 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 55.09 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 0.89 (kBtu/h) | 1.16 (kBtu/h) | 21.19 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 59.33 | 7/21 13:30:00 | 79.68 | 0.01 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 0.68 (kBtu/h) | 0.89 (kBtu/h) | 16.95 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.11 (ton) | 0.13 (ton) | 63.57 | 69.92 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 1.03 (kBtu/h) | 1.34 (kBtu/h) | 25.43 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 211.89 | 233.08 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 0.76 (kBtu/h) | 0.99 (kBtu/h) | 19.07 | 154.68 | 12/21 16:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.28 (ton) | 0.31 (ton) | 154.68 | 169.51 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 1.31 (kBtu/h) | 1.71 (kBtu/h) | 31.78 | 125.01 | 12/21 16:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.33 (ton) | 0.36 (ton) | 182.22 | 199.17 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 1.56 (kBtu/h) | 2.03 (kBtu/h) | 38.14 | 154.68 | 12/21 16:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 48.73 | 55.09 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 0.72 (kBtu/h) | 0.93 (kBtu/h) | 16.95 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 55.09 | 61.45 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 0.54 (kBtu/h) | 0.7 (kBtu/h) | 12.71 | 38.14 | 12/21 13:45:00 | 22.28 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 211.89 | 233.08 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.63 (kBtu/h) | 2.12 (kBtu/h) | 40.26 | 154.68 | 12/21 14:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 61.45 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 0.43 (kBtu/h) | 0.56 (kBtu/h) | 10.59 | 38.14 | 12/21 13:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 224.6 | 245.79 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.11 (kBtu/h) | 1.44 (kBtu/h) | 27.55 | 154.68 | 12/21 13:15:00 | 22.28 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 65.69 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 0.33 (kBtu/h) | 0.43 (kBtu/h) | 8.48 | 38.14 | 12/21 13:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 59.33 | 65.69 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 1.8 (kBtu/h) | 2.33 (kBtu/h) | 42.38 | 55.09 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.36 (ton) | 0.4 (ton) | 201.29 | 220.36 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.13 (kBtu/h) | 2.77 (kBtu/h) | 50.85 | 154.68 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 163.15 | 180.1 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.14 (kBtu/h) | 2.78 (kBtu/h) | 50.85 | 125.01 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.35 (ton) | 0.39 (ton) | 194.94 | 214.01 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.41 (kBtu/h) | 3.13 (kBtu/h) | 57.21 | 154.68 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 52.97 | 57.21 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 1.08 (kBtu/h) | 1.41 (kBtu/h) | 25.43 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 0.89 (kBtu/h) | 1.16 (kBtu/h) | 21.19 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 222.48 | 243.67 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.34 (kBtu/h) | 3.04 (kBtu/h) | 55.09 | 154.68 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 0.65 (kBtu/h) | 0.84 (kBtu/h) | 14.83 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 222.48 | 245.79 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.07 (kBtu/h) | 2.69 (kBtu/h) | 48.73 | 154.68 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 57.21 | 63.57 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 0.71 (kBtu/h) | 0.92 (kBtu/h) | 16.95 | 38.14 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 67.8 | 74.16 | 7/21 14:15:00 | 80.06 | 0.01 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 3.2 (kBtu/h) | 4.17 (kBtu/h) | 76.28 | 99.59 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 220.36 | 241.55 | 7/21 12:00:00 | 78.06 | 0.01 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 7.53 (kBtu/h) | 9.79 (kBtu/h) | 177.99 | 230.96 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.37 (ton) | 186.46 | 205.53 | 7/21 12:00:00 | 78.06 | 0.01 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 6.39 (kBtu/h) | 8.3 (kBtu/h) | 150.44 | 197.06 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.39 (ton) | 0.43 (ton) | 218.24 | 239.43 | 7/21 12:00:00 | 78.06 | 0.01 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 7.58 (kBtu/h) | 9.86 (kBtu/h) | 180.1 | 233.08 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.1 (ton) | 0.12 (ton) | 57.21 | 63.57 | 7/21 12:15:00 | 78.39 | 0.01 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 2.52 (kBtu/h) | 3.27 (kBtu/h) | 59.33 | 78.4 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.15 (ton) | 0.17 (ton) | 84.76 | 93.23 | 7/21 13:30:00 | 79.68 | 0.01 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 2.44 (kBtu/h) | 3.17 (kBtu/h) | 57.21 | 76.28 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.6 (ton) | 0.66 (ton) | 332.66 | 364.45 | 7/21 13:15:00 | 79.48 | 0.01 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 7.54 (kBtu/h) | 9.8 (kBtu/h) | 177.99 | 233.08 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.16 (ton) | 0.17 (ton) | 86.87 | 95.35 | 7/21 13:30:00 | 79.68 | 0.01 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 2.33 (kBtu/h) | 3.03 (kBtu/h) | 55.09 | 72.04 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.59 (ton) | 0.65 (ton) | 328.43 | 360.21 | 7/21 13:15:00 | 79.48 | 0.01 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 7.45 (kBtu/h) | 9.69 (kBtu/h) | 175.87 | 228.84 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.15 (ton) | 0.17 (ton) | 84.76 | 93.23 | 7/21 13:30:00 | 79.68 | 0.01 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 2.37 (kBtu/h) | 3.08 (kBtu/h) | 57.21 | 74.16 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 175.87 | 192.82 | 7/21 13:30:00 | 79.68 | 0.01 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 3.63 (kBtu/h) | 4.72 (kBtu/h) | 84.76 | 110.18 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 46.62 | 50.85 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 0.47 (kBtu/h) | 0.61 (kBtu/h) | 10.59 | 21.19 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.19 (ton) | 0.21 (ton) | 105.94 | 116.54 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.77 (kBtu/h) | 2.31 (kBtu/h) | 42.38 | 55.09 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:15:00 | 69.39 | 0.01 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Heating | 1.79 (kBtu/h) | 2.33 (kBtu/h) | 42.38 | 55.09 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Heating | 1.45 (kBtu/h) | 1.89 (kBtu/h) | 33.9 | 44.5 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Heating | 1.67 (kBtu/h) | 2.17 (kBtu/h) | 40.26 | 50.85 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 36.02 | 38.14 | 7/21 14:15:00 | 80.06 | 0.01 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Heating | 2.6 (kBtu/h) | 3.38 (kBtu/h) | 61.45 | 80.52 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 27.55 | 7/21 16:00:00 | 79.14 | 0.01 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Heating | 2.19 (kBtu/h) | 2.85 (kBtu/h) | 52.97 | 67.8 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 16:00:00 | 79.14 | 0.01 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Heating | 1.9 (kBtu/h) | 2.47 (kBtu/h) | 44.5 | 59.33 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 27.55 | 31.78 | 7/21 16:00:00 | 79.14 | 0.01 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Heating | 2.11 (kBtu/h) | 2.75 (kBtu/h) | 50.85 | 65.69 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:00:00 | 80.06 | 0.01 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Heating | 2.79 (kBtu/h) | 3.62 (kBtu/h) | 65.69 | 86.87 | 12/21 09:00:00 | 22.28 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.09 (ton) | 46.62 | 52.97 | 7/21 22:00:00 | 69.66 | 0.01 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 0.14 (kBtu/h) | 0.18 (kBtu/h) | 4.24 | 21.19 | 12/21 16:00:00 | 22.28 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Water |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.35 | COP | |
| OS:Coil:Heating:Water | Autosized | gal/min | Plant Loop | Hot Water Loop | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 68.0 to 68.0 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 32,185 | ft^2 | 42 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 42 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Make-up air unit Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialEnthalpy | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-CorridorFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,620 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr1 Sys-3 Flr-2 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr2 Sys-3 Flr-1 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr3 Sys-3 Flr-4 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr4 Sys-3 Flr-3 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-EmployeeLoungeFlr1 Sys-3 Flr-2 Sch-B HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontLoungeFlr1 Sys-3 Flr-2 Sch-H HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr1 Sys-4 Flr-2 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr2 Sys-4 Flr-1 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr3 Sys-4 Flr-4 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr4 Sys-4 Flr-3 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-LaundryRoomFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MechanicalRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MeetingRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Gas | Autosized | Btu/h | Gas Burner Efficiency | 0.80 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RestroomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:Water | Autosized | gal/min | Plant Loop | Chilled Water Loop | ||
| OS:Coil:Heating:Water | Autosized | gal/min | Plant Loop | Hot Water Loop | ||
| OS:Fan:VariableVolume | Autosized | cfm | Pressure Rise | 5.85 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 55.4 to 55.4 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 2 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:VAV:Reheat | 2 | ||||
(controls) |
||||||
| HVAC Operation Schedule | VAV with Reheat Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Chiller:Electric:EIR | 22,363.24 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 44.6 to 44.6 | F | |||
| OS:Chiller:Electric:EIR | 0.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
(demand) |
||||||
| OS:Coil:Cooling:Water | Air Loop | VAV with Reheat | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 44.60 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:CoolingTower:SingleSpeed - Air | Autosized | gal/min | ||||
| OS:CoolingTower:SingleSpeed (cont) - Water | Autosized | cfm | Fan Power at Design Air Flow Rate | 254,565.38 | W | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 84.2 to 84.2 | F | |||
(demand) |
||||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 84.20 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:VariableSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Boiler:HotWater | 506,345.20 | Btu/h | Nominal Thermal Efficiency | 0.83 | fraction | |
| OS:SetpointManager:OutdoorAirReset | ||||||
| OS:Boiler:HotWater | 0.00 | Btu/h | Nominal Thermal Efficiency | 0.85 | fraction | |
(demand) |
||||||
| OS:Coil:Heating:Water | Air Loop | Make-up air unit | ||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 1 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 2 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 3 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 4 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 5 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 6 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 7 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 8 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 9 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 10 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 11 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 12 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 13 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 14 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 15 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 16 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 17 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 18 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 19 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 20 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 21 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 22 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 23 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 24 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 25 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 26 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 27 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 28 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 29 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 30 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 31 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 32 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 33 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 34 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 35 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 36 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 37 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 38 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 39 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 40 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 41 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 42 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 43 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 44 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 45 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 46 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 47 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 48 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 49 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 50 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 51 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 52 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 53 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 54 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 55 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 56 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 57 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 58 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 59 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 60 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 61 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 62 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 63 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 64 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 65 | |||||
| OS:Coil:Heating:Water | Air Loop | VAV with Reheat | ||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 66 | |||||
| OS:Coil:Heating:Water:Baseboard | Coil Heating Water Baseboard 67 | |||||
| Air Terminal Connections | 2 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 179.60 | F | ||||
| Loop Design Temperature Difference | 28.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 0.81 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
| OS:WaterUse:Connections | Water Use Connections 37 | |||||
| OS:WaterUse:Connections | Water Use Connections 38 | |||||
| OS:WaterUse:Connections | Water Use Connections 39 | |||||
| OS:WaterUse:Connections | Water Use Connections 40 | |||||
| OS:WaterUse:Connections | Water Use Connections 41 | |||||
| OS:WaterUse:Connections | Water Use Connections 42 | |||||
| OS:WaterUse:Connections | Water Use Connections 43 | |||||
| OS:WaterUse:Connections | Water Use Connections 44 | |||||
| OS:WaterUse:Connections | Water Use Connections 45 | |||||
| OS:WaterUse:Connections | Water Use Connections 46 | |||||
| OS:WaterUse:Connections | Water Use Connections 47 | |||||
| OS:WaterUse:Connections | Water Use Connections 48 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.86 | 1.51 | 17820 | 0.332 | 0.321 | 0.026 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.438 | 0.395 | 0.027 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.437 | 0.395 | 0.03 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.424 | 0.392 | 0.25 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1782 | 4.48 | 4.358 | 0.054 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.475 | 5.326 | 0.067 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.475 | 5.326 | 0.075 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.476 | 5.326 | 0.32 | 0.0 | 0.0 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1.56 | 3.26 | 3861 | 1.027 | 0.992 | 0.051 | 0.0 | 0.0 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3.12 | 6.52 | 3861 | 1.174 | 0.0 | 0.051 | 0.0 | 0.0 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 14.67 | 16.31 | 19307 | 1.579 | 1.527 | 0.069 | 0.0 | 0.0 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3.51 | 6.53 | 15444 | 0.714 | 0.0 | 0.051 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 2376 | 0.331 | 0.32 | 0.214 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.392 | 0.268 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.392 | 0.297 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.39 | 0.536 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1485 | 0.388 | 0.375 | 0.055 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.475 | 0.459 | 0.069 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.459 | 0.076 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.46 | 0.325 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.666 | 0.592 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.665 | 0.592 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.655 | 0.591 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.685 | 0.593 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.691 | 0.593 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.822 | 0.723 | 0.189 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.849 | 0.725 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.836 | 0.725 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.833 | 0.725 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.818 | 0.724 | 0.061 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.86 | 0.726 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.863 | 0.726 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.83 | 0.725 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.877 | 0.727 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.866 | 0.726 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.807 | 0.721 | 0.209 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.836 | 0.725 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.835 | 0.724 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.832 | 0.724 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.816 | 0.723 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.856 | 0.725 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.87 | 0.726 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.831 | 0.725 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.874 | 0.726 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.858 | 0.725 | 0.068 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.78 | 0.717 | 0.442 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.807 | 0.719 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.808 | 0.719 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.807 | 0.719 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.79 | 0.719 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.808 | 0.72 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.817 | 0.72 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.799 | 0.72 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.818 | 0.72 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.81 | 0.72 | 0.291 | 0.0 | 0.0 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.62 | 0.98 | 11583 | 0.388 | 0.375 | 0.055 | 0.0 | 0.0 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.09 | 0.16 | 3861 | 0.332 | 0.321 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.23 | 0.4 | 9505 | 0.332 | 0.321 | 0.049 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 2377 | 0.336 | 0.321 | 0.214 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.413 | 0.393 | 0.269 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.412 | 0.393 | 0.297 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.414 | 0.391 | 0.536 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 2377 | 0.388 | 0.376 | 0.239 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.3 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.331 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.46 | 0.599 | 0.0 | 0.0 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.62 | 1.09 | 3861 | 0.332 | 0.321 | 0.049 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 2724964.7 | 63.1 | 63.1 |
| Net Site Energy | 2724964.7 | 63.1 | 63.1 |
| Total Source Energy | 4368100.4 | 101.1 | 101.1 |
| Net Source Energy | 4368100.4 | 101.1 | 101.1 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 67 |
| CHW Temp | Temperature | 3 | 1 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| CW Temp | Temperature | 3 | 1 |
| Make-up air unit Occ Sch | Dimensionless | 7 | 2 |
| Makeup-Air Unit Supply Air Temp | Temperature | 0 | 1 |
| NECB-A-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-A-Lighting | Dimensionless | 3 | 1 |
| NECB-A-Occupancy | Dimensionless | 3 | 1 |
| NECB-A-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-A-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-A-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| NECB-Activity | ActivityLevel | 0 | 67 |
| NECB-B-Electric-Equipment | Dimensionless | 3 | 2 |
| NECB-B-Lighting | Dimensionless | 3 | 2 |
| NECB-B-Occupancy | Dimensionless | 3 | 2 |
| NECB-B-Service Water Heating | Dimensionless | 3 | 2 |
| NECB-B-Thermostat Setpoint-Cooling | Temperature | 3 | 6 |
| NECB-B-Thermostat Setpoint-Heating | Temperature | 3 | 6 |
| NECB-C-Electric-Equipment | Dimensionless | 3 | 4 |
| NECB-C-Lighting | Dimensionless | 3 | 4 |
| NECB-C-Occupancy | Dimensionless | 3 | 4 |
| NECB-C-Thermostat Setpoint-Cooling | Temperature | 3 | 9 |
| NECB-C-Thermostat Setpoint-Heating | Temperature | 3 | 9 |
| NECB-E-Electric-Equipment | Dimensionless | 3 | 9 |
| NECB-E-Lighting | Dimensionless | 3 | 9 |
| NECB-E-Occupancy | Dimensionless | 3 | 9 |
| NECB-E-Service Water Heating | Dimensionless | 3 | 9 |
| NECB-E-Thermostat Setpoint-Cooling | Temperature | 3 | 19 |
| NECB-E-Thermostat Setpoint-Heating | Temperature | 3 | 19 |
| NECB-F-Electric-Equipment | Dimensionless | 3 | 50 |
| NECB-F-Lighting | Dimensionless | 3 | 50 |
| NECB-F-Occupancy | Dimensionless | 3 | 50 |
| NECB-F-Service Water Heating | Dimensionless | 3 | 35 |
| NECB-F-Thermostat Setpoint-Cooling | Temperature | 3 | 105 |
| NECB-F-Thermostat Setpoint-Heating | Temperature | 3 | 105 |
| NECB-H-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-H-Lighting | Dimensionless | 3 | 1 |
| NECB-H-Occupancy | Dimensionless | 3 | 1 |
| NECB-H-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-H-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-H-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| ON_OFF_ALWAYS_OFF | Availability | 3 | 42 |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 108 | 0 | 1 | |
| Schedule Ruleset 109 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 110 | 0 | 1 | |
| Schedule Ruleset 111 | 0 | 1 | |
| Schedule Ruleset 112 | 0 | 1 | |
| Schedule Ruleset 113 | 0 | 1 | |
| Schedule Ruleset 114 | 0 | 1 | |
| Schedule Ruleset 115 | 0 | 1 | |
| Schedule Ruleset 116 | 0 | 1 | |
| Schedule Ruleset 117 | 0 | 1 | |
| Schedule Ruleset 118 | 0 | 1 | |
| Schedule Ruleset 119 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 120 | 0 | 1 | |
| Schedule Ruleset 121 | 0 | 1 | |
| Schedule Ruleset 122 | 0 | 1 | |
| Schedule Ruleset 123 | 0 | 1 | |
| Schedule Ruleset 124 | 0 | 1 | |
| Schedule Ruleset 125 | 0 | 1 | |
| Schedule Ruleset 126 | 0 | 1 | |
| Schedule Ruleset 127 | 0 | 1 | |
| Schedule Ruleset 128 | 0 | 1 | |
| Schedule Ruleset 129 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 130 | 0 | 1 | |
| Schedule Ruleset 131 | 0 | 1 | |
| Schedule Ruleset 132 | 0 | 1 | |
| Schedule Ruleset 133 | 0 | 1 | |
| Schedule Ruleset 134 | 0 | 1 | |
| Schedule Ruleset 135 | 0 | 1 | |
| Schedule Ruleset 136 | 0 | 1 | |
| Schedule Ruleset 137 | 0 | 1 | |
| Schedule Ruleset 138 | 0 | 1 | |
| Schedule Ruleset 139 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 140 | 0 | 1 | |
| Schedule Ruleset 141 | 0 | 1 | |
| Schedule Ruleset 142 | 0 | 1 | |
| Schedule Ruleset 143 | 0 | 1 | |
| Schedule Ruleset 144 | 0 | 1 | |
| Schedule Ruleset 145 | 0 | 1 | |
| Schedule Ruleset 146 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Supply Air Temp | Temperature | 0 | 1 |
| VAV with Reheat Occ Sch | Dimensionless | 7 | 2 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |